AEMC 565 True RMS Clamp-on Leakage Current Meter, 60mA-100A, 600V AC/DC
Product Description
The TRMS Clamp-On Leakage Current Meter Model 565 is designed to measure low AC currents, which are typically leakage currents in ground conductors. Low currents are measured using either the 60mA or the 600mA range. The high sensitivity of the probe (10µA and 100µA) is possible through special jaw construction and, in particular, critical shielding of the jaws. At low measurement levels, this shielding out of the noise is critical for low sensitivity, accuracy, and stability.
The Model 565 can be used as a standard clamp-on meter measuring to 100Arms, as well as AC and DC voltage, resistance and continuity with a buzzer.
The Model 565 is ergonomic in design and fits well in the hand, facilitating one hand operation. The jaw size is compact yet designed to accommodate the most common conductors up to 1" (26mm) in diameter.
Overview
- Check for leakage and locate insulation breakdowns on live circuits.
- Measures leakage current up to 600mA with up to 10μA resolution.
- Measures current up to 100Arms
- Measures up to 600Vac/dc
- Measures Hz on either V or A inputs
- Measures Resistance and Continuity
- Hold feature freezes Value
- Max feature keeps track of highest measured In-rush value
- Zero button ideal for measuring relative values
- Filter to isolate 50/60Hz fundamental from harmonics
- Compatible with VDE 0404
Specifications
Voltage Range: | 600Vrms AC/DC Auto-Ranging |
Resolution Max: | 0.1V |
Current Range: | 100Arms AC |
Resolution Max: | 10µA |
Accuracy V Typical: | 1.0% ± 5cts |
Accuracy A Typical: | 1.2% ± 5cts |
Continuity: | <35Ω |
Resistance: | 1kΩ |
Frequency: | 1kHz in V, A |
∆REL: | Yes |
Power Source: | 2 x AAA, IEC LR03 |
Battery Life: | 45 hrs |
Dimensions: | 8.5 x 2.5 x 1.18" (218 x 64 x 30mm) |
Weight: | 10.0 oz. (280g) with batteries |
Jaw Opening: | 1.10" (28mm) |
Operating Temperature: | +32° to 104°F (0° to +40°C) |
Storage Temperature: | +14° to 140°F (-10° to +60°C) |
Operating Humidity: | 80% up to 104°F (40°C) |
Pollution Degree: | 2 |
Safety Compliance: | EN/IEC 61010 to 600V CAT III |
What's in the Box
- True RMS Clamp-on Leakage Current Meter
- Two color-coded 5ft test leads
- Carrying Case
- 2 AAA Batteries
- User Manual