AEMC 8510 DTR Digital Transformer Ratiometer, 110/220V
Product Description
The DTR® Model 8510 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current. The DTR® is fully automatic and uses an ANSI/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR® automatically self-calibrates and checks for open windings/connections/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.
Overview
- Ratio Testing: PT/VT from 0.8000:1 to 8000:1 and CT from 0.8000 to 1000.0 (Auto-Ranging)
 - Tests performed by exciting the primary and reading the secondary; provides safer conditions for the operator on step-down transformers
 - Continuity test indicates open or loose (high resistance) terminal connections
 - DC test mode eliminates errors due to magnetic build up
 - Stores up to 10 primary/secondary nameplate voltages to use in comparing test results
 - Displays ratio, test current, winding polarity, and deviation from nameplate voltage or ratio
 - Stores up to 10,000 test results
 - DataView® software included which allows configuring the instrument, downloading stored measurements and printing of test results in a report format
 - Display warns of incorrect lead connection, reverse polarity, open and short circuits
 
Specifications
| VT/PT Ratio Range | Auto-Ranging 0.8000:1 to 8000:1 | 
| VT/PT Accuracy* | Ratio 0.8000 to 9.9999: ±0.2% of Reading Ratio 10.000 to 999.99: ±0.1% of Reading Ratio 1000.0 to 4999.9: ±0.2% of Reading Ratio 5000.0 to 8000.0: ±0.50% of Reading  | 
| CT Ratio Range | Auto-Ranging 0.8000 to 1000.0 | 
| CT Accuracy* | Ratio 0.8000 to 1000.0: ±0.5% of Reading | 
| Excitation Signal | VT/PT Mode: 32 Vrms maximum CT Mode: 0 to 1A Auto Level, 0.1 to 5 Vrms max.  | 
| Excitation Current Display | Range: 0 to 1000 mA Accuracy: ±2% of Reading + 2mA  | 
| Excitation Frequency | 70 Hz | 
| Measurement Method | In accordance with ANSI/IEEE C57.12.90-2006 | 
| Display | LCD 16 character, 2 line, large format, LED backlight, day/night visible | 
| Languages Supported | English, Spanish, French, Italian, German, Portuguese | 
| Communication | Optically isolated USB 2.0 | 
| Data Storage | Stores up to 10,000 complete measurements | 
| *73.4°F ±9°F (23°C ± 5°C), 50 to 70% RH, full battery charge, no external fields or noise. | |
 
							
What's in the Box
- DTR Digital Transformer Ratiometer
 - NiMH Batteries (Installed)
 - 115 V Power Cord
 - 2 x 15' (4.6 m) Leads
 - 10' (3 m) USB Cable
 - External Battery Charger (90-264 V AC, 50/60 Hz)
 - DataView Software
 - Manual
 - Soft Carrying Case
 

          