{ "id":6192715169982, "title":"AEMC 8510 DTR Digital Transformer Ratiometer, 110\/220V","handle":"aemc-8510-dtr-digital-transformer-ratiometer-110-220v", "description":"\u003cp\u003e\u003cspan\u003eThe DTR\u003c\/span\u003e\u003csup\u003e®\u003c\/sup\u003e\u003cspan\u003e Model 8510 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR\u003c\/span\u003e\u003csup\u003e®\u003c\/sup\u003e\u003cspan\u003e Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current. The DTR\u003c\/span\u003e\u003csup\u003e®\u003c\/sup\u003e\u003cspan\u003e is fully automatic and uses an ANSI\/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR\u003c\/span\u003e\u003csup\u003e®\u003c\/sup\u003e\u003cspan\u003e automatically self-calibrates and checks for open windings\/connections\/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.\u003c\/span\u003e\u003c\/p\u003e\n\u003cp\u003e\u003c!-- split --\u003e\u003c\/p\u003e\n\u003ch2 class=\"hidden\"\u003eOverview\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003eRatio Testing: PT\/VT from 0.8000:1 to 8000:1 and CT from 0.8000 to 1000.0 (Auto-Ranging) \u003c\/li\u003e\n\u003cli\u003eTests performed by exciting the primary and reading the secondary; provides safer conditions for the operator on step-down transformers\u003c\/li\u003e\n\u003cli\u003eContinuity test indicates open or loose (high resistance) terminal connections\u003c\/li\u003e\n\u003cli\u003eDC test mode eliminates errors due to magnetic build up\u003c\/li\u003e\n\u003cli\u003eStores up to 10 primary\/secondary nameplate voltages to use in comparing test results\u003c\/li\u003e\n\u003cli\u003eDisplays ratio, test current, winding polarity, and deviation from nameplate voltage or ratio\u003c\/li\u003e\n\u003cli\u003eStores up to 10,000 test results\u003c\/li\u003e\n\u003cli\u003eDataView\u003csup\u003e®\u003c\/sup\u003e\u003cspan\u003e \u003c\/span\u003esoftware included which allows configuring the instrument, downloading stored measurements and printing of test results in a report format\u003c\/li\u003e\n\u003cli\u003eDisplay warns of incorrect lead connection, reverse polarity, open and short circuits\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c!-- split --\u003e\n\u003ch2 class=\"hidden\"\u003eSpecifications\u003c\/h2\u003e\n\u003ctable class=\"table table-striped\"\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eVT\/PT Ratio Range\u003c\/td\u003e\n\u003ctd\u003eAuto-Ranging 0.8000:1 to 8000:1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVT\/PT Accuracy*\u003c\/td\u003e\n\u003ctd\u003eRatio 0.8000 to 9.9999: ±0.2% of Reading\u003cbr\u003eRatio 10.000 to 999.99: ±0.1% of Reading\u003cbr\u003eRatio 1000.0 to 4999.9: ±0.2% of Reading\u003cbr\u003eRatio 5000.0 to 8000.0: ±0.50% of Reading\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCT Ratio Range\u003c\/td\u003e\n\u003ctd\u003eAuto-Ranging 0.8000 to 1000.0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCT Accuracy*\u003c\/td\u003e\n\u003ctd\u003eRatio 0.8000 to 1000.0: ±0.5% of Reading\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExcitation Signal\u003c\/td\u003e\n\u003ctd\u003eVT\/PT Mode: 32 Vrms maximum\u003cbr\u003eCT Mode: 0 to 1A Auto Level, 0.1 to 5 Vrms max.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExcitation Current Display\u003c\/td\u003e\n\u003ctd\u003eRange: 0 to 1000 mA\u003cbr\u003eAccuracy: ±2% of Reading + 2mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExcitation Frequency\u003c\/td\u003e\n\u003ctd\u003e70 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasurement Method\u003c\/td\u003e\n\u003ctd\u003eIn accordance with ANSI\/IEEE C57.12.90-2006\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay\u003c\/td\u003e\n\u003ctd\u003eLCD 16 character, 2 line, large format, LED backlight, day\/night visible\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLanguages Supported\u003c\/td\u003e\n\u003ctd\u003eEnglish, Spanish, French, Italian, German, Portuguese\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication\u003c\/td\u003e\n\u003ctd\u003eOptically isolated USB 2.0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eData Storage\u003c\/td\u003e\n\u003ctd\u003eStores up to 10,000 complete measurements\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd colspan=\"2\"\u003e*73.4°F ±9°F (23°C ± 5°C), 50 to 70% RH, full battery charge, no external fields or noise.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003e\u003cbr\u003e \u003c!-- split --\u003e\u003c\/p\u003e\n\u003ch2 class=\"hidden\"\u003eWhat's in the Box\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003eDTR Digital Transformer Ratiometer\u003c\/li\u003e\n\u003cli\u003eNiMH Batteries (Installed)\u003c\/li\u003e\n\u003cli\u003e115 V Power Cord\u003c\/li\u003e\n\u003cli\u003e2 x 15' (4.6 m) Leads\u003c\/li\u003e\n\u003cli\u003e10' (3 m) USB Cable\u003c\/li\u003e\n\u003cli\u003eExternal Battery Charger (90-264 V AC, 50\/60 Hz)\u003c\/li\u003e\n\u003cli\u003eDataView Software\u003c\/li\u003e\n\u003cli\u003eManual\u003c\/li\u003e\n\u003cli\u003eSoft Carrying Case\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c!-- split --\u003e\n\u003ch2 class=\"hidden\"\u003eResources\u003c\/h2\u003e\n\u003cp\u003e\u003ca href=\"https:\/\/cdn.shopify.com\/s\/files\/1\/2663\/3750\/files\/AEMC_8510_-_2136-50.pdf?v=1611689274\" target=\"_blank\" title=\"AEMC 8510 DTR Spec Sheet\" rel=\"noopener noreferrer\"\u003eAEMC 8510 DTR Spec Sheet\u003c\/a\u003e\u003c\/p\u003e", "published_at":"2021-01-26T12:49:21", "created_at":"2021-01-26T12:49:20", "vendor":"AEMC Instruments", "type":"Transformer Testers", "tags":[], "price":486500, "price_min":486500, "price_max":486500, "price_varies":false, "compare_at_price":null, "compare_at_price_min":0, "compare_at_price_max":0, "compare_at_price_varies":true, "all_variant_ids":[37964348391614], "variants":[{ "id":37964348391614, "product_id":6192715169982, "product_handle":"aemc-8510-dtr-digital-transformer-ratiometer-110-220v", "title":"Default Title", "option1":"Default Title", "option2":null, "option3":null, "sku":"AEMC-2136.50", "requires_shipping":true, "taxable":true, "featured_image":null,"image_id":null, "available":true, "name":"AEMC 8510 DTR Digital Transformer Ratiometer, 110\/220V - Default Title", "options":["Default Title"], "price":486500, "weight":16329, "compare_at_price":null, "inventory_quantity":0, "inventory_management":"shopify", "inventory_policy":"continue", "inventory_in_cart":0, "inventory_remaining":0, "incoming":false, "next_incoming_date":null, "taxable":true, "barcode":"685338160062"}], "available":true,"images":["\/\/kingswayinstruments.com\/cdn\/shop\/products\/AEMC8510Pic1.png?v=1611690563"],"featured_image":"\/\/kingswayinstruments.com\/cdn\/shop\/products\/AEMC8510Pic1.png?v=1611690563", "options":["Title"], "url":"\/products\/aemc-8510-dtr-digital-transformer-ratiometer-110-220v"}

AEMC 8510 DTR Digital Transformer Ratiometer, 110/220V

Product Description

The DTR® Model 8510 is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current. The DTR® is fully automatic and uses an ANSI/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR® automatically self-calibrates and checks for open windings/connections/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.

Sku: AEMC-2136.50
On Back-Order
$4,865.00 CAD

  • Ratio Testing: PT/VT from 0.8000:1 to 8000:1 and CT from 0.8000 to 1000.0 (Auto-Ranging) 
  • Tests performed by exciting the primary and reading the secondary; provides safer conditions for the operator on step-down transformers
  • Continuity test indicates open or loose (high resistance) terminal connections
  • DC test mode eliminates errors due to magnetic build up
  • Stores up to 10 primary/secondary nameplate voltages to use in comparing test results
  • Displays ratio, test current, winding polarity, and deviation from nameplate voltage or ratio
  • Stores up to 10,000 test results
  • DataView® software included which allows configuring the instrument, downloading stored measurements and printing of test results in a report format
  • Display warns of incorrect lead connection, reverse polarity, open and short circuits
VT/PT Ratio Range Auto-Ranging 0.8000:1 to 8000:1
VT/PT Accuracy* Ratio 0.8000 to 9.9999: ±0.2% of Reading
Ratio 10.000 to 999.99: ±0.1% of Reading
Ratio 1000.0 to 4999.9: ±0.2% of Reading
Ratio 5000.0 to 8000.0: ±0.50% of Reading
CT Ratio Range Auto-Ranging 0.8000 to 1000.0
CT Accuracy* Ratio 0.8000 to 1000.0: ±0.5% of Reading
Excitation Signal VT/PT Mode: 32 Vrms maximum
CT Mode: 0 to 1A Auto Level, 0.1 to 5 Vrms max.
Excitation Current Display Range: 0 to 1000 mA
Accuracy: ±2% of Reading + 2mA
Excitation Frequency 70 Hz
Measurement Method In accordance with ANSI/IEEE C57.12.90-2006
Display LCD 16 character, 2 line, large format, LED backlight, day/night visible
Languages Supported English, Spanish, French, Italian, German, Portuguese
Communication Optically isolated USB 2.0
Data Storage Stores up to 10,000 complete measurements
*73.4°F ±9°F (23°C ± 5°C), 50 to 70% RH, full battery charge, no external fields or noise.


  • DTR Digital Transformer Ratiometer
  • NiMH Batteries (Installed)
  • 115 V Power Cord
  • 2 x 15' (4.6 m) Leads
  • 10' (3 m) USB Cable
  • External Battery Charger (90-264 V AC, 50/60 Hz)
  • DataView Software
  • Manual
  • Soft Carrying Case

Related Products